i have compact rio 9076 4 different modules: ni-9205 (analog input), ni-9264(analog output), ni-9402 (bidirectional digital i/o), ni-9403 (bidirectional digital i/o). have several 3rd party sensors: sensirion sfm3000 (mass flow sensor) 5v , first-sensor hdi0611arz8p5 (pressure sensor) 5v, oval rv21 (reed magnetic proximity sensor) 10v , humidity sensor 5v.

i wish power them using moudules output. of them require 5v , 1 require 10v. can modules?

for of sensor require communicate using i2c protocol require in/out port , pull-up ressistor. modules include pull-up ressistor inside? referance voltage them? , how should enable it?

also oval rv21 (reed magnetic proximity sensor) require pull-down ressitor, modules include pull-down ressistor inside? referance voltage them? , how should enable it?

thank or hirshfeld mechatronics engineer אור הירשפלד

thank got answer ni support

in general, possible power sensors using ao ni-9264 since acts floating voltage supply. can out put voltage in ranges specifies however, should consider fact output current of module (current drive) 16mv. if enough sensors, should ok.

ni-9264 specs http://www.ni.com/pdf/manuals/374404e.pdf

unfortunately, none of modules mentioned have pull-up resistor.

the ni-9403 has pull-down resistor on channels , reference voltage 0.8v. can see specification of module in attached link.

ni-9403 specs http://www.ni.com/pdf/manuals/374069e.pdf